Property |
Type |
Description |
Active Circuit[1-8] |
Enumerated |
This is the status of the condenser circuits reported by the controller. This indicates if each stage 1-8 is present or not, and if it is on or off: |
Air Flow Override: Tracer |
Multi-State |
Used to communicate override commands for air valve. In Tracer Summit version 15 and newer this property can not be read (you'll see '???' displayed) because it only initiates an air flow override. |
Air Flow Stpnt: Active Min |
Float |
This property represents the active minimum flow setpoint read from the VAV. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0-65,534 L/s |
Air Flow Stpnt: Active Min Sourc |
Enumerated |
This property indicates which minimum is enforcing the “Air Flow Stpnt: Active Min” property. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: |
Air Flow Stpnt: Min Local Heat |
Float |
Defines the minimum flow through the VAV that is necessary to safely operate the reheat capability of a VAV with reheat. This value must be less than or equal to the “Heating Maximum Flow” property. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10, 000 L/s (0 – 21,189 cfm) |
Air Flow Stpnt: Min Standby Heat |
Float |
Defines the minimum flow setpoint while in the occupied standby heating mode. This value must be less than or equal to the “Heating Maximum Flow” property. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Valid Range: 0 – 10, 000 L/s (0 – 21,189 cfm) |
Air Flow Stpnt: Tracer |
Float |
This is the measured supply airflow, typically provided by a flow sensor. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Ventilation Flow Controller or Flow Tracking Controller. Valid Range: 0 – 65,000 L/s (0 – 137,728 cfm) |
Air Valve Position |
Float |
This property represents the cool output valve position (if valid) or the primary heat output valve position (if valid) of the VAV. If both cooling position and primary heating position values are reported from the VAV the BCU will report the greater of the two values. Valid Range: 0 – 100% |
Air Valve Drive Closed: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. This property indicates the value to be used by the BCU to communicate override commands for the Air Flow Override. 0 = Auto |
Air Valve Drive Max: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. This property indicates the value to be used by the BCU to communicate override commands for the Air Flow Override. 0 = Auto |
Air Valve Drive Min: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. This property indicates the value to be used by the BCU to communicate override commands for the Air Flow Override. 0 = Auto |
Air Valve Drive Open: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. This property indicates the value to be used by the BCU to communicate override commands for the Air Flow Override. 0 = Auto |
Airflow: Active |
Numeric |
This property indicates the active airflow, if the UCM has a local or communicated airflow value. |
Alarm Event Class |
Numeric |
This arrayed property specifies the event classes to which Informational Message and Service Required alarm messages are routed. The event class has a set of receivers as determined in Site Configuration that will receive the alarm messages. |
Alarm Present |
Binary |
This indicates that the unit has a diagnostic 0 = No diagnostics |
Alarm Reset |
Binary |
Used to directly set nviRequest, enumeration 10 (clear alarm). The alarm state of the object is cleared, but the state of the object itself may remain unchanged. Persistent alarms will be reported, as they are re-detected. '???' will be displayed because this is handled as a momentary command state, so there is no real value that can be read. The range below is more for an object like a binary output that is used to reference the Alarm Reset property. Valid Range: 0 = reset disabled (default value) |
Alarms Locked |
Binary |
The value of this property is TRUE when clearing alarms remotely is not supported by the UCM. 0 = (False) Clear alarm request is supported |
Application Mode: Tracer |
Multi-State |
Used to communicate the application mode of the unit. Valid Range: 1 = Heat |
Autocommissioning Cmd: Tracer |
Enumerated |
This property is used by the BCU to command the VAV to execute its autocommissioning sequence. Full use of this function requires the presence of an auxiliary temperature sensor in the discharge air stream (without it the fan and reheat operation cannot be tested). This property can not be read (you'll see '???' displayed) because it only initiates the autocommissioning command. This property applies only to a Trane VAV box. Valid Range: 0 = Begin After Staggered Delay |
Autocommissioning Air Valve Pos[1-2] |
Float |
This property is used to report the air valve positions measured during the last autocommissioning sequence. The VAV keeps the results until another autocommissioning sequence is run. This property applies only to Trane VAV boxes. Array element definitions: Valid range for each array element: |
Autocommissioning Disch Air Temp[1-7] |
Float |
This property is used to report the discharge air temperatures measured during the last autocommissioning sequence. The VAV keeps the results until another autocommissioning sequence is run. This property applies only to Trane VAV boxes. Array element definitions: [1] = fan flow initial temperature (i.e. temperature while fan in VAV is off and air valve is open to cooling max), Typical range for each array element: |
Autocommissioning State |
Enumerated |
This property is used to indicate the status of an auto commission sequence. This property applies only to a Trane VAV box. Valid Range: 0 = Waiting |
Autocommissioning Time Stamp |
Date/Time Numeric |
This property is used to report the date and time of the last autocommissioning sequence. The VAV stores the results until another autocommissioning sequence is run. This property applies only to Trane VAV boxes. |
Auxiliary Heat Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Auxiliary Heat Enable Input. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. 0 = Disable all stages |
Auxiliary Heat Control: Tracer |
Binary |
Used to enable/disable all stages of auxiliary heat in the controller. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. 0 = Disable all stages |
Cabinet Style |
Multi-State |
Defines the cabinet style based on the Unit Type. |
Comm5 Communication State |
Numeric |
Obsolete name as of v16SP2. Refer to LonTalk Communication State property for a description. |
Comm5 Device NID |
Bytestring |
Obsolete name as of v16SP2. Refer to LonTalk Device NID property for a description. |
Comm5 DSN |
Unsignedlongword |
Obsolete name as of v16SP2. Refer to LonTalk DSN property for a description. |
Comm5 Program ID |
Numeric |
Obsolete name as of v16SP2. Refer to LonTalk Program ID property for a description. |
Communication Channel |
Numeric |
This property provides access to the assigned communications channel value of the UCM being represented. |
Compressor Control: Loop Control |
Binary |
Used to propagate an immediate and latched compressor disable to the controller. If its' value is "disable," this sets Compressor Control: Tracer and the VM-based value to disable. Auto only causes the VM-based value to be set to auto. (The BCU will evaluate the VM-based value along with other factors to set the Compressor Control: Tracer to auto.) Valid Range: 0 = Disable, |
Compressor Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Compressor Enable Input. 0 = Disable |
Compressor Control: Tracer |
Binary |
Used to communicate the compressor enable input to the controller. 0 = Disable |
Condenser Type |
Enumerated |
Condenser type. Valid range: 0 = none |
Condenser Water Flow Status |
Boolean |
The local or communicated condenser water flow. Valid Range: 0 = no flow, |
Condenser Water Pump Output |
Boolean |
The hardwired condenser water pump status. Valid Range: |
Condenser Water Temp Entering |
Float |
The local temperature of the water entering the condenser. |
Condenser Water Temp Leaving |
Float |
The local temperature of the water leaving the condenser. |
Configuration: Unit Type Profile |
Multi-State |
Defines the type of unit. All devices that meet the SCC Profile use this property. 0 = Generic |
Configuration: Unit Type Trane |
Multi-State |
Defines the type of unit. This property is used for Trane products only. 0 = 1 Heat/1 Cool |
Control Event Class |
Numeric |
This property determines where control messages are routed when the object's present value is controlled. |
Cool Output |
Numeric |
Status of the unit's cool capacity (if hydronic, report valve position of cool valve). Range: 0 to 100% |
Cool Setpoint High Limit |
Numeric |
The local or communicated occupied cooling setpoint high limit. If both exist, the communicated value has priority. Range: 40.00 to 115.00°F (4.44 to 46.11°C) |
Cool Setpoint Occupied |
Numeric |
This property defines the occupied cooling setpoint. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 40.00 to 115.00°F (4.44 to 46.11°C) |
Cool Setpoint Occupied Standby |
Numeric |
This property defines the occupied standby cooling setpoint. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 40.00 to 115.00°F (4.44 to 46.11°C) |
Cool Setpoint Unoccupied |
Numeric |
This property defines the unoccupied cooling setpoint. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 40.00 to 115.00°F (4.44 to 46.11°C) |
Cool Stage Status[1-8] |
Multi-State |
Indicates if cool stage 1-8 is present or not, and if it is on or off. 0 = Off 1 = On 2 = Not Present |
Cool Type |
Multi-State |
Defines the cool type of the unit. 0 = None |
Cooling Setpoint Low Limit |
Numeric |
The local or communicated occupied cooling setpoint low limit If both exist, the communicated value has priority. Range: 40.00 to 115.00°F (4.44 to 46.11°C) |
Cooling Setpoint Shift: Ref |
Property Reference |
This property indicates the value to be used by the BCU to shift the occupied and occupied standby cooling setpoints. Unoccupied cooling setpoints are not shifted. Range: -18.0 to 18.0°F (-10.0 to 10.0°C degrees) |
Cooling Setpoint Shift: Tracer |
Numeric |
Used to shift the occupied and occupied standby cooling setpoints. Unoccupied cooling setpoints are not shifted. Range: -180 to 180 F degrees (-10.0 to 10.0°C degrees) |
Critical Application Alarming |
Binary |
This property changes a select group of priority 2 alarms (service request) to priority 3 alarms (critical). This pre- defined group of alarms may vary for each UCM. 0 = Disabled (default) |
Default Cooling Fan Cycling |
Binary |
Defines the default fan cycling operation of the unit in cooling modes. 0 = Cycling Fan in Cooling |
Default Cooling Fan Speed |
Multi-State |
Defines the default fan speed operation of the unit in cooling modes. 0 = Not Used |
Default Heating Fan Cycling |
Binary |
Defines the default fan cycling operation of the unit in heating modes. 0 = Cycling Fan in Heating |
Default Heating Fan Speed |
Multi-State |
Defines the default fan speed operation of the unit in heating modes. 0 = Not Used |
Defrost Status |
Enumerated |
This property is used to report when the unit is in defrost mode. Valid Range: 0 = Not defrosting 1 = Defrosting 2 = Not present |
Dehumidification Control Status |
Multi-State |
Indicates if dehumidification (for 1 state only – the 1st stage) is present or not present, and if it is on or off. Valid Range: 0 = Off 1 = On 2 = Not Present |
Device Major Revision |
UnsignedByte |
This defines the major revision number for the device. The major revision of the device is updated whenever the network interface of the device changes. |
Device Minor Revision |
UnsignedByte |
This defines the minor revision number for the device. The minor revision of the device is updated whenever the software is changed for any reason. |
Diagnostic Alarm Status |
Text String |
Communicates the diagnostic messages of the controller as they occur. |
Discharge Air Temp |
Numeric |
Status of the hardwired sensor on the unit. Range: -40.00 to 212.00°F (-40.00 to 100.00 °C) |
Display Active Setpoint |
Binary |
Allows the active space temperature setpoint in the UCM to be displayed at the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = “No” (Do Not Display) 1 = “Yes” (Display) |
Display Active Space Temp |
Binary |
Allows the active space temperature in the UCM to be displayed at the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = “No” (Do Not Display) 1 = “Yes” (Display) |
Economizer Control: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Economizer Enable Input. 0 = Disabled |
Economizer Control: Tracer |
Multi-State |
This property indicates the value that will be communicated by the system to the UCM and used enable and disable the economizer control. 0 = Disabled |
Economizer Damper Position |
Numeric |
Status of unit's economizer damper position. (Not used if unit has 2-position OA damper) Range: 0-100% |
Economizer Enable: Active |
Multi-State |
This property reports whether it is even possible for the unit to economize, if one is present. (See 'Economizer Status' property for its on/off status). 0 = Disabled |
Economizer Min Position: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Economizer Minimum Position Input. Range: 0 to 100 % |
Economizer Min Position: Tracer |
Numeric |
This property indicates the value that will be communicated by the system to the UCM and used as the minimum position of the outdoor air damper. Range = 0 to 100% |
Economizer Minimum Position Occupied |
Numeric |
Indicates the outdoor air damper occupied minimum position: Range: 0 to 100% |
Economizer Minimum Position Occupied Standby |
Numeric |
Indicates the outdoor air damper occupied standby minimum position. Range: 0 to 100% |
Economizer Status |
Multi-State |
Used to display the status of the economizer, if present. The state of this property is dependent upon the state of the 'Economizer Enable: Active' property. 0 = Closed (disabled) |
Economizer/Ventilation Type |
Multi-State |
Defines the economizer/ventilation type of the unit. 0 = None |
Electric Heat Run Hours |
Numeric |
Number of electric heat run hours elapsed since the "Electric Heat Counter" has been cleared. This property only applies to Trane controllers. Range: 0 to 65535 hours. |
Emergency Override: Request |
Multi-State |
This property is used to override the UCM's Present Value, when an emergency signal dictates the need for the following functions. 0 = Normal |
Emergency Override: Tracer |
Multi-State |
Used to communicate the emergency override request to the controller. Note: If Emergency Override: Request is Normal, the communicated request will come from the Present Value. The communicated request will come from Emergency Override: Request if it is anything other than Normal 0 = Normal |
Energy Hold Off: Active |
Binary |
Used to report the status of the energy hold off in the controller. 0 = Normal |
Entering Water Temp: Tracer (Name obsoleted in v14) |
Numeric |
See 'Source Temperature: Tracer' |
Entering Water Temperature: Active |
Numeric |
The local or communicated entering water temperature. When both exist, the communicated value has priority. Range: 32.00 to 212.00°F (0.00 to 100.00°C) |
Entering Water Temperature: Ref (Name obsoleted in v14) |
Property Reference |
See 'Source Temperature: Ref' |
Exhaust Status |
Real |
This property indicates active status of the binary output controlling the exhaust fan Range: 0 – 100% |
Exhaust/Return Type |
Multi-State |
Defines the exhaust/return type of the unit. 0 = None |
External Interface File (XIF) |
Text |
The logical interface to a device, which contains the Program Interface. A device's external interface specifies the number and types of LonMark objects; the number, types, directions and connection attributes of network variables; and the number of message tags. The program ID field is used as the key to identify each external interface. |
Face And Bypass: Active |
Numeric |
Status of the unit's face and bypass damper. Range: 0 to 100% 0% = Full Bypass |
Fan Speed: Ref |
Numeric |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the fan speed. The fan being controlled may be a 1, 2, 3, or variable speed fan. This property is valid for non-VAV devices only. Valid Range: 0 – 100%. A state of “Not Used” (0xFF) specifies that the associated network variable is in “auto”. |
Fan Speed: Tracer |
Numeric |
Used to communicate the fan speed to the UCM. The fan being controlled may be a 1, 2, 3, or variable speed fan. This property is valid for non-VAV devices only. Valid Range: 0 – 100%. A state of 0xFF specifies that the associated network variable is in “auto”. |
Flow Gain |
Numeric |
Indicates the air flow measurement gain. Range: 0 to 327,675 |
Flow Setpoint: Active |
Numeric |
This property indicates the active flow setpoint, if the UCM has a local or communicated flow setpoint value. Range: 0 – 138,840 CFM (0 to 65,534L/s) |
Generic Analog Input |
Numeric |
The state of generic analog input. This property only applies to Trane controllers. Range: 0 – 100 |
Generic Binary Input |
Multi-State |
The state of generic binary input 1. 0 = Off |
Generic Binary Output |
Multi-State |
The state of generic binary output 1. 0 = Off |
Generic Binary Output: Tracer |
Binary |
Used to control the generic binary output. (when present) 0 = Off 1 = On |
Generic Temperature |
Numeric |
Status of the local generic temperature input. Range: -40.00 to 158.00°F (-40.00 to 70.00°C) |
Heat Output |
Numeric |
Status of the unit's primary heat capacity (if hydronic, reports valve position of primary heat valve). Range: 0 to 100% |
Heat Output Secondary |
Numeric |
Status of the unit's secondary heat capacity (if hydronic, report valve position of secondary heat valve). For a Trane VAV box this represents the reheat output in the controller (electric or hydronic). Range: 0 to 100% |
Heat Setpoint High Limit |
Numeric |
The local or communicated occupied heating setpoint high limit If both exist, the communicated value has priority Range: 40.00 to 115.00°F (44.4 to 46.11°C) |
Heat Setpoint Low Limit |
Numeric |
The local or communicated occupied heating setpoint low limit If both exist, the communicated value has priority Range: 40.00 to 115.00°F (44.4 to 46.11°C) |
Heat Setpoint Occupied |
Numeric |
This property defines the occupied heating setpoint. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 40.00 to 115.00 deg F (44.4 to 46.11 °C) |
Heat Setpoint Occupied Standby |
Numeric |
This property defines the occupied standby heating setpoint. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 40.00 to 115.00°F (44.4 to 46.11°C) |
Heat Setpoint Unoccupied |
Numeric |
This property defines the unoccupied heating setpoint. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 40.00 to 115.00°F (44.4 to 46.11°C) |
Heat Stage Status[1-8] |
Multi-State |
Indicates if heat stage 1-8 is present or not, and if it is on or off. 0 = Off |
Heat/Cool Mode: Active |
Binary |
Used to display the current heat/cool mode of the SCC UCM. This is an interpretation made by the BCU based on the value shown for the 'Mode: Heat/Cool' property Valid Range: 0 = Heating, 1 = Cooling. Mode: Heat/Cool (Display Text): 0 = Auto (Cooling) 5 = Pre Cool (Cooling) |
Heat/Cool Mode: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the heat/cool mode. |
Heating Maximum Flow |
Numeric |
Indicates the heating maximum air flow. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 0 to 138,840 CFM (0 to 65534 L/s) |
Heating Minimum Flow |
Numeric |
Indicates the heating minimum air flow. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 0 to 138,840 CFM (0 to 65534 L/s) |
Heating Setpoint Shift: Ref |
Property Reference |
This property indicates the value to be used by the BCU to shift the occupied and occupied standby heating setpoints. Unoccupied heating setpoints are not shifted. Range: -18.0 to +18.0 F degrees (-100 to 100°C) |
Heating Setpoint Shift: Tracer |
Numeric |
Used to shift the occupied and occupied standby heating setpoints. Unoccupied heating setpoints are not shifted. Range: -18.0 to +18.0°F (-10.0 to 10.0°C) |
Humidifier: Active |
Numeric |
Status of unit's humidifier output. Range: 0-100% 0% = Off |
Language Identifier |
Multi-State |
Defines which language is currently being used. It defines for the UCM what language to present alarm messages in. 0 = English |
Last Control Date Time |
Date/Time Numeric |
This indicates the date and time when the present value property of this object was last controlled. |
Leaving Water Temperature: Active |
Numeric |
The local leaving water temperature. Range: -40.00 to 212.00°F (-40.00 to 100.00°C |
Light 1 Command: Local |
Binary |
Reports how light circuit #1 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Off 1 = On |
Light 1 Command: Tracer |
Binary |
Used to communicate override commands to light circuit #1. This property can not be read, it only controls an override for light #1. This property only applies to Trane controllers (e.g., the ZN523) Valid Range: 0 = Off |
Light 1 Status |
Binary |
Reports the status of light circuit #1. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: |
Light 2 Command: Local |
Binary |
Reports how light circuit #2 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Off 1 = On |
Light 2 Command: Tracer |
Binary |
Used to communicate override commands to light circuit #2. This property can not be read, it only controls an override for light #2. This property only applies to Trane controllers (e.g., the ZN523) Valid Range: 0 = Off 1 = On Invalid value = 0xFF |
Light 2 Status |
Binary |
Reports the status of light circuit #2. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Off 1 = On |
Load: Absolute |
Numeric |
Used by heat pumps to indicate the current energy consumed by the unit. Range: 0 to 1,865 tons (0 to 6553.4 KW) |
Load: Terminal |
Numeric |
Used by Heat Pumps to indicate the current heat/cool energy demand of the unit. Range: -150% = (Screaming for heat) |
Location Label |
Text String |
Used to provide descriptive location information. |
LonTalk Communication State |
Numeric |
This property indicates the status of communications between the BCU and the SCC. 0 = Down 1 = Up 2 = No neuron ID assigned 3 = Installation in progress 4 = Incomplete bindings |
LonTalk Device NID |
Bytestring |
The Neuron ID (NID) of the UCM. This is a unique, 12 digit, non-adjustable serial number found on every Neuron chip. |
LonTalk DSN |
Unsignedlongword |
A comma-separated value representing the domain, subnet, and node ID (DSN) of the UCM. |
LonTalk Program ID |
Numeric |
An identifier stored in the device (in the Neuron Chip's EEPROM) that identifies the application program running on the node. All nodes with the same program ID must have the same external interface. |
Maintenance Requested |
Multi-State |
This property is used to report whether a service ping has been received by the UCM (e.g a zone sensor initiated a service ping on a ZN523). This property only applies to Trane controllers. Valid Range: 0 = No 1 = Yes 2 = Not Present |
Manual Control |
Binary |
If the UCM supports this property this will indicate if the source of the control parameters used by the device is local (manual). Valid Range: FALSE (0) = device is under building management control (default). TRUE (non-0) = device is under manual control. |
Maximum Flow |
Numeric |
Indicates the maximum air flow. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 0 to 138,840 CFM (0 to 65534 L/s) |
Minimum Flow |
Numeric |
Indicates the minimum air flow. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 0 to 138,840 CFM (0 to 65534 L/s) |
Minimum Off Time |
Numeric |
This property provides access to the minimum off time assigned to the UCM being represented. This value serves to protect the hardware from cycle times that might harm the hardware. |
Minimum On Time |
Numeric |
This property provides access to the minimum on time assigned to the UCM being represented. This value serves to protect the hardware from cycle times that might harm the hardware. |
Minimum Send Time |
Numeric |
This defines the minimum period of time between automatic network variable output transmissions. Although this configuration property is optional, it must be provided if the minimum send time function is used in the controller. Setting this property to 0.0 disables the Minimum Send Time mechanism. Valid Range: 0.0 sec to 6,553.4 sec. |
Minimum Time Remaining |
Numeric |
This property provides access to the minimum time remaining (if any) of a minimum On/Off time control action for the represented UCM device. PUTS are also allowed so that an operator can intervene on a Minimum On/Off control action that is in progress. |
Mixed Air Temperature |
NUMERIC |
Controller property that displays the unit's current mixed air temperature. Typical Range: 4.0 to 122.0 deg. F (-20.00 to 50.00 deg C). Invalid: 327.67 |
Mode: Active |
Multi-State |
Actual mode of the unit. Valid Range: 1 = Heat |
Mode: Heat/Cool |
Multi-State |
Actual heat/cool mode of the unit. Valid Range: 1 = Heat |
Mode: Occupancy |
Multi-State |
The local or communicated occupancy status When both exist, the communicated value. has priority 0 = Occupied |
Node Self Doc |
Text String |
This property displays the unit's type of UCM (i.e. ZN510, MP580, VV550, etc.). |
Node Status |
Multi-State |
The current operating condition of the Neuron Microprocessor. Possible conditions are: Normal Unconfigured Unconfigured/No application Configured/Online Configured/Offline (soft) Configured/Offline (hard) Configured/Offline (bypass) Unsupported |
Nominal Flow |
Numeric |
Indicates the nominal air flow. Range: 0 to 138,840 CFM (0 to 65534 L/s) |
Object Identifier |
Object ID |
This property allows the assignment of a unique printable name to the object for user identification. |
Object Name |
Text String |
This property allows the assignment of a unique printable name to the object for user identification. |
Object Type |
Multi-State |
This property Designates the object's type (i.e. analog input, binary input, TCM, PCM, etc). |
Occupancy: Active |
Binary |
Used to display the current occupancy of the SCC UCM based on the multi-state values of the 'Mode: Occupancy' property (nvoEffectOccup from the UCM). Valid Range: 0 = Unoccupied, |
Occupancy: Tracer |
Enumerated |
This property indicates the value that is communicated by the system to the UCM and used to determine occupancy. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. 0=Unoccupied |
Occupant Call: Local |
Multi-State |
This property is used to report whether an occupant call has been received at the UCM (e.g. a ZN523) from a zone sensor. This property only applies to Trane controllers. Valid Range: 0 = No 1 = Yes 2 = Not Present |
Occupied Bypass Time |
Numeric |
Defines the maximum amount of time that the unit can be in Bypass (occupancy) mode from a single Bypass request from a local (hardwired) switch. This property only applies to a local input, if present. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 0 to 240 minute |
Occupied Bypass: Active |
Binary |
Used to display the current occupied status of the SCC UCM based on the multi-state values of the 'Mode: Occupancy' property (nvoEffectOccup from the UCM). Valid Range: 0 = not in Occupied Bypass |
Outdoor Air Damper Position |
Numeric |
This property indicates the active position of the outdoor air damper (if the unit is configured for one). If the outdoor air damper is a modulating air damper, the valid range is between 0 and 100%. If it is a 2-position outdoor air damper, the value that appears will be either 0 or 100% (closed or open). |
Outdoor Air Enthalpy |
Numeric |
The local or communicated outdoor air enthalpy. When both exist, the communicated value has priority. Typical Range: 8.60 to 42.99 BTU/lb (20 to 100 KJoules/Kg). |
Outdoor Air Humidity: Input |
Numeric |
This property indicates the outdoor air relative humidity in a percentage, if the UCM has a locally wired humidity sensor. Range: 0% to 100% |
Outdoor Air Humidity: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Outdoor Air Humidity Input. Range: 0% to 100% |
Outdoor Air Humidity: Tracer |
Numeric |
Used to communicate outdoor air humidity to the controller. Communicated value used over local value when both are present. Range: 0% to 100% |
Outdoor Air Temp Setpoint: Local |
Numeric |
Defines the outside air temperature at which the device is allowed to economize. This is the absolute temperature, not a differential temp or enthalpy value. Valid Range: 32 – 100 degF (0.00 – 37.78 degC) |
Outdoor Air Temperature: Active |
Float |
The local or communicated outdoor air temperature. When both exist, the communicated value has priority. Valid Range: -40.00 to 158.00 deg. F (-40.00 to 70.00 deg. .C) |
Outdoor Air Temperature: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the Outdoor Air Temperature. |
Outdoor Air Temperature: Tracer |
Numeric |
This property indicates the value that is communicated by the system to the UCM and used as the Outdoor Air Temperature. Range = -40 to 158 degrees F (-40 to 70 degrees C) |
Preheat Type |
Multi-State |
Defines the preheat type of the unit. 0 = None |
Present Value |
Op Mode |
This property is used to control the unit to one of nine standard operation modes. These modes are defined as UNOCCUPIED, OPTIMAL START, OCCUPIED, OPTIMAL STOP, DEMAND LIMIT, DUTY CYCLE, PRIORITY SHUTDOWN, NIGHT ECONOMIZE, and NIGHT HEAT- COOL. A translation (within the BCU) may take place to map these modes into a simpler mode set. |
Reheat Type |
Multi-State |
Defines the reheat type of the unit. 0 = None |
Release Overrides: Tracer |
Multi-State |
Used to release one or more overrides. This property only applies to Trane controllers (e.g., the ZN523). Valid values for this property: 0 = Temperature Setpoint Release |
Reset Electric Heat Timer |
Binary |
Used to reset the electric heat timer in the UCM (e.g., the ZN523). Valid Range: 0 = Off |
Reset Maintenance Timer |
Binary |
Used to reset the maintenance timer in the SCC UCM. 0 = Off |
Return Air Temperature |
Numeric |
The return air temperature. Valid Range: -40.00 to 212.00 deg. F (-40.00 to 100.00 deg. C). |
Reversing Valve |
Binary |
This property indicates the active status of the reversing valve (applies to Water Source Heat Pumps only). 0=Off/Heat |
Saturated Condenser Temperature |
Float |
The active condenser temperature reported from the UCM. |
Setpoint Offset: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Setpoint Offset. |
Setpoint Offset: Tracer |
Numeric |
Used to shift the occupied and standby temperature setpoint. All setpoints will be shifted up or down by this value. |
Source Temperature: Ref (Formerly called 'Entering Water Temperature: Ref') |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Entering Water Temperature Input for a non-VAV controller or as the Supply Air Temperature Input for a VAV controller. Valid Range: 32.00 to 212.00 deg. F (0.00 to 100.00 deg. C). |
Source Temperature: Tracer (Formerly called 'Entering Water Temperature: Tracer') |
Numeric |
Used to communicate the entering water temperature to a non-VAV controller or the supply air temperature to a VAV controller. The communicated value is used over the local value when both are present. Valid Range: 32.00 to 212.00 deg. F (0 to 100 C) |
Space CO2 Concentration: Input |
Numeric |
This property indicates the space carbon dioxide (CO2) concentration in parts per million (ppm), if the UCM has a locally wired CO2 sensor. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Range: 0 to 5000 ppm |
Space CO2 Concentration: Ref |
Numeric |
This property indicates the value to be used by the BCU to determine which value to communicate to the UCM as the Space CO2 reading. The communicated value will take precedence over a locally hard-wired sensor. |
Space CO2 Concentration: Tracer |
Numeric |
If used, this is the value that will be communicated down to the UCM and used as its Space CO2 reading. The communicated value will take precedence over a locally hard-wired sensor. |
Space CO2 Limit |
Numeric |
This defines a high limit CO2 setpoint for the controlled space. Typical Range: 300 to 3000 ppm. A value of 0 ppm will disable the CO2 Limit functions in the controller. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Default Value: 0 (no limit functions) |
Space CO2 Low Limit |
Numeric |
This defines a high limit CO2 setpoint for the controlled space. Typical Range: 0 to 2000 ppm. A value of 0 ppm will disable the CO2 Limit functions in the controller. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Default Value: 0 (no limit functions) |
Space Dehumidification Setpoint: Local |
Numeric |
This defines a high limit humidity setpoint for the controlled space. Typical Range: 40 to 100%. A value of 0% will disable the dehumidification functions in the controller. Default Value: 0% (no dehumidification functions) |
Space Humidity: Input |
Numeric |
This property indicates the space relative humidity in a percentage, if the UCM has a locally wired humidity sensor. Range: 0% to 100% |
Space Pressure: Active |
Float |
The local or communicated effective space pressure. When both exist, the communicated value has priority. Typical Range: -1.00 to 1.00 I.W.C. (-250 to 250 Pa). |
Space Setpoint User |
Numeric |
This is a graphical setpoint field that applies during the occupied and occupied standby mode. It is the space setpoint that the user intends to send down to the UCM as the active setpoint. An algorithm uses the heat/cool mode and occupancy mode of the UCM to determine the necessary 'Space Temperature Setpoint: Ref' value that will equate the users entered value to the 'Space Temperature Setpoint: Active' property in the UCM. The algorithm is based on the asymmetrical method for determining the active setpoint relative to the communicated space setpoint value. The valid range entered in this field will vary depending on the default heating/cooling setpoints, setpoint offset, and setpoint shift parameters, but is such that it will not cause the 'Space Temperature Setpoint: Ref' value to go out of range. |
Space Temperature: Active |
Numeric |
The local or communicated effective space temperature. When both exist, the communicated value has priority. If neither exist, the unit uses its stored default. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Typical Range: 14.00 to 122.00°F (-10 to 50°C) |
Space Temperature: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Space Temperature. Range: 14.00 to 122.00°F (-10 to 50°C) |
Space Temperature: Tracer |
Numeric |
Used to communicate a space temperature to the controller. Communicated value used over local value when both are present. Range: 14 to 122°F (-10 to 50°C) |
Space Temperature Setpoint Control: Local |
Binary |
Defines whether the local hardwired setpoint input is enabled or disabled. 0=Disabled |
Space Temperature Setpoint: Active |
Numeric |
The local or communicated effective space temperature setpoint. When both exist, the communicated value has priority. If neither exists, the unit uses its stored default value. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 50.00 to 95.00°F (10.00 to 35.00°C) |
Space Temperature Setpoint: Local |
Numeric |
Reflects the local setpoint input. |
Space Temperature Setpoint: Ref |
Property Reference |
This property indicates the value to be used by the BCU to determine which value to communicate as the Space Temperature Setpoint. Range: 50.00 to 95.00°F (10.00 to 35.00°C) |
Space Temperature Setpoint: Tracer |
Numeric |
Used to communicate a space temperature setpoint to the controller. Communicated value used over local value when both are present. Range: 50.00 to 95.00°F (10.00 to 35.00°C) |
Standby Minimum Flow |
Numeric |
Indicates the standby minimum air flow. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller. Range: 0 to 138,840 CFM (0 to 65534 L/s) |
Startup Setpoint |
Numeric |
This property defines the threshold for warm-up or pre-cool at start-up. |
Startup Time Delay |
Unsigned Word |
Represents the amount of time the controller waits (after power-up) before invoking the normal control algorithm operation. Range: 0 to 6553.5 s |
Sunblind 1 Command: Local |
Binary |
Reports how sunblind circuit #1 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g. the ZN523). Valid Range: |
Sunblind 1 Command: Tracer |
Binary |
Used to communicate override commands to sunblind circuit #1. This property can not be read, it only controls an override for sunblind #1. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Close |
Sunblind 1 Status |
Binary |
Reports the status of sunblind circuit #1. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Closed |
Sunblind 2 Command: Local |
Binary |
Reports how sunblind circuit #2 is being commanded from the zone sensor. This property only applies to Trane controllers (e.g. the ZN523). Valid Range: 0 = Closed |
Sunblind 2 Command: Tracer |
Binary |
Used to communicate override commands to sunblind circuit #2. This property can not be read, it only controls an override for sunblind #2. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Close |
Sunblind 2 Status |
Binary |
Reports the status of sunblind circuit #2. This property only applies to Trane controllers (e.g., the ZN523). Valid Range: 0 = Closed |
Supply Fan Proving Status |
Enumerated |
Status that indicates if the supply fan is actually on, compared to the Supply Fan Status property, which may indicate only a requested state. Example of proving actual operation is by means of a current sensing relay on the wires to the fan motor. 0 = Off |
Supply Fan Run Time |
Numeric |
Number of fan run hours elapsed since the "maintenance required" diagnostic was initiated and cleared. Range: 0 to 65535 h |
Supply Fan Speed |
Enumerated |
Status of unit's fan output as an enumeration. Valid Range: Percent = Enum = Display Text 0% = 0 = Off |
Supply Fan Status |
Numeric |
Status of unit's fans output. Range: 0 – 100% |
Supply Fan Switch Control: Local |
Binary |
Defines whether the local hardwired setpoint input is enabled or disabled. 0=Disabled |
Supply Fan Type |
Multi-State |
Defines the supply fan type of the unit 0 = None |
Timed Override Request |
Binary |
This property indicates the active status of the Timed Override Flag, which is set, when the Timed Override button is pushed on the zone sensor. 0=No (not pressed) |
Timed Override Request: Cancel |
Binary |
This property indicates the active status of the Cancel Timed Override Flag that is set when the cancel button is pushed on the zone sensor. 0=No (not pressed) |
Update Tag |
Numeric |
This property is used as the upload/download tag. Its purpose is to keep the PC Workstation and BCU copies of the object instance in synchronization |
VAV Drive Max Heat: Ref |
Property Reference |
This property indicates the value to be used by the BCU to communicate Max Heat override commands for the Application Mode. 0 = Auto |
Ventilation Ratio Calc |
Float |
This status property is the ratio between the “Ventilation Setpoint: Active” property and the “Airflow: Active” property. This value is limited by the “Ventilation Ratio Limit: Tracer” property. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 100% |
Ventilation Ratio Limit: Tracer |
Float |
This property is communicated to the VAV as the limit to request outdoor air in the primary air (VAV system). This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 1 – 100% |
Ventilation Setpoint: Active |
Float |
This property is the amount of outdoor air the VAV is requesting. The VAV will typically use this in determining the “Ventilation Ratio Calc” property. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 65,534 L/s |
Ventilation Setpoint: Max |
Float |
This property is the maximum flow of outdoor air the space should ever require for ventilation purposes. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
Ventilation Setpoint: Min |
Float |
This property is the minimum flow of outdoor air required to ventilate the space during periods of zero occupancy. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
Ventilation Setpoint: Ref |
Float |
This property is communicated to the VAV as the ventilation setpoint (the outdoor air requirement) for the expected number of people occupying the space. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
Ventilation Setpoint: Tracer |
Float |
This property is communicated to the VAV as the ventilation setpoint (the outdoor air requirement) for the expected number of people occupying the space. This property only applies to a Trane VAV box with its cabinet style configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 – 10,000 L/s (0 – 21,189 cfm) |
Water Valve Drive Closed: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. This property indicates the value to be used by the BCU to communicate override commands for the Water Valve Override. 0 = Auto 1 = Close all valves |
Water Valve Drive Open: Ref |
Property Reference |
This property only applies to sites that use a v14.XXX BCU image or older. This property indicates the value to be used by the BCU to communicate override commands for the Water Valve Override. 0 = Auto 1 = Open all valves |
Water Valve Override: Tracer |
Multi-State |
Used to communicate override commands for the Water Valve(s). In Tracer Summit version 15 and newer this property can not be read, it only initiates a water valve override. If the controller is a Trane VAV box then this property only affects the operation of the controller if its cabinet style is configured as Space Temperature Controller or Ventilation Flow Controller. Valid Range: 0 = Normal |